Jitter, resonance or intermittent abnormal noise occurs after the circular air duct is installed. The reason may be pipe support, interface misalignment, valve operation or fan transmission vibration. You cannot just add a boom near the vibration point. First record the fan frequency, valve opening, vibration occurrence time and pipe section position, and then compare it with the drawings, bracket layout and equipment interfaces. Determining whether changes occur as equipment starts and stops can help distinguish airflow noise from structural vibration.Let’s start with the looseness and spacing of the supports and hangers.
Check the boom nuts, cross arms, hoops and fixed points along the line for looseness, slippage, deformation or collision with the building structure. If the contact surface of the bracket is insufficient or the pipe clamp form does not match the round pipe, rolling or local shaking may occur during operation. The support spacing and connection method should be confirmed according to the design and conditions such as pipe diameter, weight, insulation, etc. Do not encrypt the supports based on on-site feelings alone; when adding new supports, the load-bearing structure and maintenance space must also be confirmed.
Check joint alignment; do not force misaligned sections together.
Observe whether the center lines are aligned at flanges, clamps, elbows, reducers and equipment interfaces, and whether the pipe section is twisted due to the elevation difference of the hanging point. If bolts or clamps are used to forcibly pull the offset pipe fittings together during connection, the elastic force will be released during operation and amplify the vibration. If necessary, review the measurement datum and installation dimensions, first adjust the position of the support and pipe section, and then connect according to regulations; for the fan interface, it is also necessary to confirm whether the flexible connection required by the design is installed correctly and has sufficient margin for movement.
Pay attention to fans, valves and airflow changes
If the vibration mainly changes with the fan speed or valve opening, the airflow conditions near the equipment fixation, soft joints, air valves and elbows should be checked. The soft joints cannot be pulled too tight, flattened or supported by other components, and the damper blades and actuators should also be installed according to the direction. Foreign matter in the pipe, clogging of the filter, or changes in system resistance may cause the air volume to deviate from the design value. This needs to be judged based on debugging data. Do not cover up the noise by closing multiple valves.
After rectification, retest under the same working conditions.
Record the same fan frequency, valve status and measuring point location before and after the inspection, and compare whether the vibration or sound has changed. When rectification involves equipment foundation, load-bearing components or structural connections, it should be evaluated by relevant professionals to avoid drilling holes or transferring loads to inappropriate locations. During acceptance, not only the sound should be listened to, but also the appearance of the pipe, interface sealing, support stability and system air volume should be confirmed to meet the project requirements.
For long-distance pipelines, the natural frequency of the pipeline, equipment speed and support stiffness may also jointly affect resonance, and single-point reinforcement may not be able to solve the vibration of the entire line. If the changes are concentrated in a certain speed range, the equipment frequency, vibration position and operation records should be provided to the equipment and designers for analysis to avoid new stress concentrations caused by over-reinforcement. If abnormal noise is accompanied by friction, cracks or equipment abnormalities, the machine should be shut down for inspection according to on-site safety requirements. The specific bracket layout, vibration isolation methods and vibration determination indicators are based on the design documents and equipment data. Complete records also facilitate subsequent maintenance.